Acceptance Test Results - With Results of Competitive Products
   
U.S.Forest Specification 5100-306a. 
For: Flame Guard Gel
 
 
Performed by: US Forest Service Laboratory
 
  + Biodegradability Tests to Protect the Environment
  + Fish Toxicity Tests to Protect the Environment
  + Mammalian Toxicity Tests To Protect Humans
  + Cleveland Open Point Flash Point 
  + Lateral Ignition and Flame Spread Tests
  + Final Corrosion Tests by 90-day Weight Loss Test
  + Initial Corrosion Tests by 90-day Weight Loss Test
     
 

Biodegradability Tests to Protect the Environment

OPPTS 835.3110(m) and OECD 301B

Biodegradability tests were performed in accordance with OPPTS 835.3110(m) and OECD 301B.  In one case natural inoculum was used and in the other a commercial inoculum (Polyseed) was used.

Test Results 

Flame Guard Gel with OPPTS 835.3110(m) was 62% biodegraded and with OECD 301B was 66 % biodegraded in 28 days. These tests were preformed with a mixture ratio of 1 pound of Flame Guard Gel Powder to 1.7 gallons of water (1 to 1.7).

USFS has classified Flame Guard Gel as: Readily Biodegradable.”

 

Actual use of Flame Guard Gel as a retardant would not be a ratio of 1 lb to 1.7 gallons. Instead it would be from a mixture ratio of from 1 lb to 5 gallons up to 1 lb, to 8 gallons.

 

FLAME GUARD GEL  . . 66% IN 28 DAYS - READILY BIODEGRADABLE

THERMO GEL  . . . . . . . 45% AT 42 DAYS - BIODEGRADABLE

NO CHAR . . . . . . . . . . . 25% AT 42 DAYS MAXIMUM– NOT BIODEGRADABLE

NO FIRE ICE . . . . . . . . .13 % AT 21 DAYS MAXIMUM– NOT BIODEGRADABLE

 

Fish Toxicity Tests to Protect the Environment

The test results - 96 hours LC 50> 1000 mg/L for rainbow trout (60 days past hatching) in ASTM in soft water LC50 is the concentration of an agent in water, expressed as milligrams per liter of solution, that results in the death of 50 percent of aquatic test specimens within a specified time frame.

In the case of these tests, the exposure is 96 hours.  The fish, and the agent, are exposed in ASTM soft water.  This is simply a standard amount of defined chemicals added to distilled water so that it is consistent regardless of who is doing the test.

 

Test Results: Acceptable 

Note: Based on the requirements in the USFS specification, Flame Guard Gel with a ratio of .6 lbs to 1 gallon of water (or 1 lb to 1.7 gallons) had acceptable performance. This ratio is very severe since the working application ratio of Flame Guard Gel would be more in the order of 1 lb to 8 gallons.

FLAME GUARD GEL . . . .1000 MG/L - ACCEPTABLE
 
THERMO GEL . . . . . . . . .28 MG/L - ACCEPTABLE

NO CHAR E-112 . . . . . . . 61 MG/L -  38 MG/L ACCEPTABLE

NO FIRE ICE  . . . . . . . . . NO REPORT

This means it will take 1000 milligrams of Flame Guard Gel at a ratio of 1 to 1.7 in one liter of water to kill 50% of the rainbow trout in 96 hours. Higher ratios, 1 to 5, 1 to 6, 1 to 8 will take more than 1000 Milligrams of Flame Guard Gel.

 

Mammalian Toxicity Tests To Protect Humans

Test Results

Acute Oral Toxicity - Concentrate - Required  >500 mg/Kg –

Performance >5050mg/Kg

USFS: Acceptable

 

FLAME GUARD GEL . . . . . Performance >5050mg/Kg

THERMO GEL . . . . . . . . . . Performance>5000 mg/Kg

NO CHAR  E112 . . . . . . . . .Performance>5050 mg/Kg

NO FIRE ICE . . . . . . . . . . . Performance>5050 mg/Kg

 

Acute Oral Toxicity- Mixed Fire Chemical - Required >5000mg/Kg

Performance >5050mg/Kg

USFS: Acceptable

 

FLAME GUARD GEL . . . . . Performance >5050mg/Kg

THERMO GEL . . . . . . . . . . Performance >5000mg/Kg

NO CHAR   E112 . . . . . . . . Performance>5050 mg/Kg

NO FIRE ICE . . . . . . . . . . . Performance>5050 mg/Kg

 

Acute Dermal Toxicity - Concentrate – Required >2000mg/Kg

Performance >2020mg/Kg

USFS: Acceptable

 

FLAME GUARD GEL . . . . . Performance >2020mg/Kg

THERMO GEL . . . . . . . . . . Performance >2020mg/Kg

NO CHAR   E112 . . . . . . . . Performance>2020 mg/Kg

NO FIRE ICE . . . . . . . . . . . Performance>2020 mg/Kg

 

 
Acute Dermal Toxicity -Mixed Fire Chemical– Required >2000mg/Kg

Performance >2020mg/Kg

USFS: Acceptable

 

FLAME GUARD GEL . . . . . Performance >2020mg/Kg

THERMO GEL . . . . . . . . . . Performance >2020mg/Kg

NO CHAR   E112 . . . . . . . . Performance>2020 mg/Kg

NO FIRE ICE . . . . . . . . . . . Performance>2020 mg/Kg

 

 

Primary Eye Irritation–Unwashed Eyes-Concentrate-
Required - Mildly irritating

Performance – Practically non-irritating

USFS: Acceptable – Toxicity category IV

Irritation score 0.7

 

FLAME GUARD GEL . . . . . Practically non-irritating  Irritation score 0.7

THERMO GEL . . . . . . . . . . Severely  irritating  Irritation score 32.0

NO CHAR   E112 . . . . . . . . Mildly irritating   Irritation Score 15.7

NO FIRE ICE . . . . . . . . . . . Moderately irritating  Irritation Score 2.7

 

Primary Eye Irritation-Unwashed Eyes-Mixed Fire Chemical

Required – Mildly irritating

Performance – Mildly irritating

USFS: Acceptable – Toxicity category IV

Irritation Score 8.0

 

FLAME GUARD GEL . . . . . Mildly irritating - Irritation Score 8.0

THERMO GEL . . . . . . . . . . Practically non-irritating  Score 1.7

NO CHAR   E112 . . . . . . . . Minimally irritating  Score 3.3

NO FIRE ICE . . . . . . . . . . . Practically non-irritating  Score 0.3 

 

Primary Eye Irritation-Washed Eyes-Concentrate

Required – Mildly irritating

Performance – Minimally irritating

USFS: Acceptable – Toxicity category IV

Irritation Score 1.3

 

FLAME GUARD GEL . . . . . Minimally irritating  Irritation Score 1.3

THERMO GEL . . . . . . . . . . Mildly irritating   Irritation Score 15.3

NO CHAR   E112 . . . . . . . . Mildly irritating   Irritation Score 8.7

NO FIRE ICE . . . . . . . . . . . Minimally irritating Irritation Score 2.7 

 

Primary Eye Irritation-Washed Eyes-Mixed Fire Chemical

Required – Mildly irritating

Performance –Mildly irritating

USFS: Acceptable – Toxicity category IV                                                             

Irritation Score 17.3

 

FLAME GUARD GEL . . . . . Mildly irritating Irritation Score 17.3

THERMO GEL . . . . . . . . . . Non irritating  Irritation Score 0.0

NO CHAR   E112 . . . . . . . . Practically non irritating  Score 0.7

NO FIRE ICE . . . . . . . . . . . Minimally irritating Irritation Score 3.3 

 
 
Primary Dermal Irritation Concentrate-Required- Mildly irritating Score <5.0                                                                     

Performance-Score 0.8 Slight irritant                                                                      

USFS: Acceptable

 

FLAME GUARD GEL . . . . . Slight irritant Score 0.8

THERMO GEL . . . . . . . . . . Slight irritant Score 0.6

NO CHAR   E112 . . . . . . . . Moderate irritant Score 2.2

NO FIRE ICE . . . . . . . . . . . Non-irritating Score 0.0

 

Primary Dermal Irritation Mixed Fire Chemical

Required-Mildly irritating Score <5.0                                                                                                                     

Performance-Score 0.8 Slight irritant                                                                      

USFS: Acceptable

Based upon the satisfactory test results a review by the Forest Service Safety and Health Branch was not required.

 

FLAME GUARD GEL . . . . . Slight irritant  Score 0.8 

THERMO GEL . . . . . . . . . . Slight irritant  Score 0.2

NO CHAR   E112 . . . . . . . . Slight irritant  Score 0.2

NO FIRE ICE . . . . . . . . . . . Non-irritating Score 0.0


Cleveland Open Point Flash Point 

Tests for Product Performance

Test results: did not produce a flash point or a fire point.

USFS Rated: Acceptable Performance.

Flash Point is the minimum temperature of a product at which it gives off vapor sufficient to form an ignitable mixture of a gas near the surface of the liquid under specified environmental conditions.

As you heat a product if gives off vapors some of which may be flammable. 

The flash point is the temperature when enough of the flammable gases are produced to actually generate a momentary flame.

The open cup part means that this test is performed in the open environment rather than a closed system.

The safety issues here are that these products are used when it is very hot and they are often poured, transferred, or used near hot engines.  If a product has a low flash point the potential is greater for accidents and injury as the product gives off flammable vapor.

 

FLAME GUARD GEL . . . . . Did not produce a flash point or a fire point. 

THERMO GEL . . . . . . . . . . No data

NO CHAR   E112 . . . . . . . . No data

NO FIRE ICE . . . . . . . . . . . No data

      

Lateral Ignition and Flame Spread Tests 

Tests For Product Performance 

Underwriters Laboratories Inc., performed fire tests for Lateral Ignition and Flame

Spread (LIFT) under contract with the U.S.Forest Services.

Test results

Using UL Standard UL 1321 Flame Guard Gel offered significant resistance before the second layer of the substrates ignited. The top layer charred with no visible flames. Instead the second layer ignited at 42 and 50 minutes through the cracks in the top layer. The performance of Flame Guard Gel as a retardant was far superior to foams and elastomers and superior to other gels tested. The USFS conducts this test for informational purposes only.

 

FLAME GUARD GEL . . . . . (23) NO IGNITION OVER 42 and 50 MINUTES. 

THERMO GEL . . . . . . . . . . (14)  10.00 – 18.35 – 14.05 – 27.52 MINUTES

NO CHAR   E112 . . . . . . . . NO TEST

NO FIRE ICE . . . . . . . . . . . ( 1 )  IGNITION  AT 28.04 – 33.30 – 42.40 Minutes

 

Final Corrosion Tests by 90-day Weight Loss Test

FGG Material Tested with Mixture 0.6 lbs/ 1 gallon of water 

After one-year storage of Mixture

 

2024-T3 Aluminum,

Aluminum Corrosion Test Results 
 
                    
Aluminum Total Immersion 70F

FGG. . . . . . . . . . . . . . . . . 0.3 mils per year

NO CHAR  (FRESH) . . . . . .0.1

NO CHAR  (3%) . . . . . . .  . 0.1

THERMO GEL (MISS) . . . . .0.11

THERMO GEL (SD) . . . . . . 0.10      

FIRE OUT ICE (0.6%) . . . . . 0.51

 

Aluminum Total Immersion 120F

 

FGG . . . . . . . . . .  . . . . . .  0.1 mils per year

NO CHAR  (FRESH) . . . . . . 0.1

NO CHAR  (3%) . . . . . .  . . . 0.1

THERMO GEL (MISS) . . . . . 0.25

THERMO GEL (SD)  . . . . . .  0.26      

FIRE OUT ICE (0.6%) . . . . .  1.90

 

Aluminum Partial Immersion 70F

FGG  . . . . . . . . . . . . . . . .   0.3 mils per year

NO CHAR  (FRESH) . . . . . .  0.1

NO CHAR  (3%) . . . . . . .  . . .0.1

THERMO GEL (MISS) . . . . .  0.08

THERMO GEL (SD) . . . . . . . .0.09      

FIRE OUT ICE (0.6%) . . . . . . 0.30

 

Aluminum Partial Immersion 120F

FGG . . . . . . . . . . . . . . . . . . . 0.1 mils per year

NO CHAR (FRESH) . . . . . . . . 0.1

NO CHAR (3%) . . . . . . . . . . . .0.1                     

THERMO GEL (MISS) . . . . . . .0.13

THERMO GEL (SD) . . . . . . . . 0.15      

FIRE OUT ICE (0.6%) . . . . . . .0.92

 

 

4130 Mild Steel

Corrosion Test Results


Mild Steel Total Immersion 70F

FGG  . . . . . . . . . . . . . . . . . 0.3 mils per year

NO CHAR  (FRESH) . . . . . . .0.1

NO CHAR  (3%) . . . . . . . . . . 0.1

THERMO GEL (MISS) . . . . . .0.05

THERMO GEL (SD). . . . . . . . 0.05      

FIRE OUT ICE (0.6%) . . . . . . 0.51

 

Mild Steel Total Immersion 120F

 

FGG . . . . . . . . . . . . . . . . . 0.1 mils per year

NO CHAR  (FRESH) . . . . . . 0.1

NO CHAR  (3%) . . . . . . . . . .0.1

THERMO GEL (MISS). . . . . .0.25

THERMO GEL (SD) . . . . . . . 0.26      

FIRE OUT ICE (0.6%) . . . . . . 1.90

 

Mild Steel Partial Immersion 70F

FGG . . . . . . . . . . . . . . . . . .1.5 mils per year

NO CHAR - FRESH . . . . . . . 0.1

NO CHAR – 3%  . . . . . . . . . .0.1

THERMO GEL (MISS) . . . . . .0.20

THERMO GEL (SD) . . . . . . . .0.35      

FIRE OUT ICE (0.6%) . . . . . . 1.90

 

Mild Steel Partial Immersion 120F

FGG . . . . . . . . . . . . . . . . . .0.3 mils per year

NO CHAR  (FRESH)  . . . . . . 0.1

NO CHAR  (3%) . . . . . . . . . . 0.1

THERMO GEL (MISS) . . . . . .0.51

THERMO GEL (SD) . . . . . . .  0.56      

FIRE OUT ICE (0.6%) . . . . . . 0.51

 

Yellow Brass Corrosion Test Results 

Yellow Brass Total Immersion 70F

FGG . . . .  . . . . . . .  . . . .  . .0.1 mils per year

NO CHAR  (FRESH) . . . . . . . 0.1

NO CHAR  (3%) . . . . . . . . . . 0.1

THERMO GEL (MISS) . . . . . .0.1

THERMO GEL (SD) . . . . . . . .0.05      

FIRE OUT ICE (0.6%) . . . . . . .0.51

 

Yellow Brass Total Immersion 120F

FGG . . . . . . . . . . . . . . . . . . .0.1 mils per year

 

NO CHAR  (FRESH) . . . . . . .  0.1

NO CHAR  (3%) . . . . . . . . . . .0.1

THERMO GEL (MISS) . . . . . . 0.14

THERMO GEL (SD) . . . . . . .  .0.16      

FIRE OUT ICE (0.6%) . . . . . . .1.90

 


Yellow
Brass Total Immersion 70F

FGG . . . . . . . . . . . . . . . . . . 0.2 mils per year

NO CHAR  (FRESH) . . . . . . . 0.1

NO CHAR  (3%) . . . . . . . . . .  0.1

THERMO GEL (MISS) . . . . . . 0.08

THERMO GEL (SD) . . . . . . . . 0.04      

FIRE OUT ICE (0.6%) . . . . . . .0.51

 

Yellow Brass Total Immersion 120F

FGG . . . . . . .  . . . . .  . . . . . .0.3 mils per year

NO CHAR  (FRESH). . . . . . . . 0.1

NO CHAR  (3%). . . . . . .  . . . 0.1

THERMO GEL (MISS). . . . . . .0.13

THERMO GEL (SD). . . . .  . . .0.10      

FIRE OUT ICE (0.6%). . . . . . .1.90

 

Initial Corrosion Tests by 90-day Weight Loss Test

Tested with Mixture 0.6 lbs/ 1 gallon of water 

Material Tested: 2024-T3 Aluminum

4130 Mild Steel,

Yellow Brass.

 

FLAME GUARD GEL. . . . . .  USFS classified results as ACCEPTABLE-

THERMO GEL . . . . . . . . . . Not Tested

NO CHAR . . . . . . . . . . . . . . Not Tested

NO FIRE ICE . . . . . . . . . . . . Not Tested 

 

 
Return to Top of Page
 
 
 
 
 
 

 

 
     